Comprehensive Power Quality Improvement Solution

Media and Communications Industry: Oriental Pearl TV Tower

夜晚的东方明珠

 

Case Introduction:High harmonics and excessive neutral current eliminate potential risks.

电能检测现场图

 

On-site Test Results:The main sources of harmonics are landscape lights and LED advertising screens, which have large current fluctuations and rapid changes. The concentrated loads generate 3Nth harmonic currents, and the neutral current is very large.

 

Test location: LED load main input terminal

Led负载 电压趋势图

Voltage trend chart

Led负载 电流趋势图

Current trend chart (blue represents neutral wire current)

Led负载 谐波电流趋势图

 

Harmonic current trend chart (blue represents the third harmonic current in the neutral line)

Led负载 谐波电流分布图

Harmonic current distribution chart

 

典型瞬时值 功率及功率因数

典型瞬时值 电压及电流波形

Power and power factor

Voltage & current waveform

典型瞬时值 电压及电压畸变率

典型瞬时值 电流及电流畸变率

Voltage and voltage distortion rate

Current and current distortion rate

典型瞬时值 A相电流畸变列表

典型瞬时值 B相电流畸变列表

Phase A current distortion list

Phase B current distortion list

典型瞬时值 C相电流畸变列表

典型瞬时值 N相电流畸变列表

Phase C current distortion list

Phase N current distortion list

 

Solution:Based on the actual site conditions and measurement data, we recommend using our PQC power quality comprehensive treatment device, which can simultaneously address power quality issues such as harmonics, three-phase imbalance, and reactive power. We will install it in the original location according to the existing cabinet space dimensions.

 

Photos Of The Mitigation Equipment Installation:

现场安装设备图3

现场设备安装图2

 

Comparison Of Mitigation Data:

治理前:三相电流波形有畸变

治理后:三相电流波形趋于正弦波

Before mitigation:

The three-phase current waveforms were distorted.

After mitigation:

The three-phase current waveform tends to be sinusoidal.

治理前:a相3次谐波电流含量30.41 A

治理后:a相3次谐波电流含量5.52 A

 

Before mitigation:

Phase A 3rd harmonic current content: 30.41A

Phase A 5th harmonic current content: 19.70A

Phase A 7th harmonic current content: 9.22A

Phase A 9th harmonic current content: 2.07A

Phase A 11th harmonic current content: 5.75A

 

 

After mitigation:

Phase A 3rd harmonic current content 5.52A

Phase A 5th harmonic current content 3.28A

Phase A 7th harmonic current content 2.44A

Phase A 9th harmonic current content 1.08A

Phase A 11th harmonic current content 2.03A

 

治理前:n相基波电流含量12.17 A

治理后:n相基波含量11.08 A

 

Before mitigation:

N-phase fundamental current: 12.17A

N-phase 3rd harmonic current: 93.01A

N-phase 5th harmonic current: 3.07A

N-phase 9th harmonic current: 8.07A

 

 

After mitigation:

N-phase fundamental current content 11.08A

N-phase 3rd harmonic current content 16.16A

N-phase 5th harmonic current content 1.62A

N-phase 9th harmonic current content 3.52A

 

 

Mitigation Result:Harmonics generated by landscape lighting and LEDs have been mitigated, and current in the neutral wire has been eliminated.