Pharmaceutical Industry: Jiangsu Taikang Biopharmaceutical Co., Ltd.

清晰后的泰康生物门头照

 

 

Case Introduction:The company's power system had excessive harmonics, affecting the normal operation of equipment and causing communication interruption between the HMI and PLC.

现场设备图

 

 

On-site Test Results:The detected harmonic currents are all quite large, with current distortion rates reaching 35% to 45%. Harmonics can affect other loads under the same transformer, especially causing malfunctions or communication interruptions to precision control instruments.

现场检测图

 

Test location: Main incoming line terminal of AC-CHP cabinet

Ac Chp谐波电流趋势图1

Harmonic current trend

 

Ac Chp谐波电流分布图1

Harmonic current distribution

 

Ac Chp电流波形图

Current waveform

Ac Chp谐波电流清单

List of harmonic currents

Ac Chp电流畸变率

Current distortion rate

Ac Chp电压畸变率

Voltage distortion rate

 

Test location: Main incoming line terminal of AN501 cabinet

A N501谐波电流趋势图

Harmonic current trend

 

A N501谐波电流分布图

Harmonic current distribution

 

A N501电流波形图

Current waveform

A N501谐波电流清单

List of harmonic currents

A N501电流畸变率

Current distortion rate

A N501电压畸变率

Voltage distortion rate

 

Test location: Main incoming line terminal of AN601 cabinet

A N601谐波电流趋势图

Harmonic current trend

 

A N601谐波电流分布图

Harmonic current distribution

 

A N601电流波形图

Current waveform

A N601谐波电流清单

List of harmonic currents

A N601电流畸变率

Current distortion rate

A N601电压畸变率

Voltage distortion rate

 

Solution:Based on the actual site conditions, the first floor is a rented public transformer, which should not be altered without authorization. Considering the available space, it is recommended to use a wall-mounted APF for on-site treatment. In addition, to eliminate high-frequency harmonics and electromagnetic interference, it is recommended to install a filter at the PLC power supply input terminal.

 

Photos Of The Mitigation Equipment Installation:

现场治理设备图

清晰后的泰康现场治理现场图

 

Comparison Of Mitigation Data:

Location:AN601

治理前后数据对比a N601(治理前:三相电流波形有畸变)

治理前后数据对比a N601(治理后:三相电流波形趋于正弦波)

Before mitigation:

The three-phase current waveforms were distorted.

After mitigation:

The three-phase current waveform tends to be sinusoidal.

 

A N601治理前:电流总畸变率35%左右

A N601治理后:电流总畸变率8%左右

Before mitigation:

Total current distortion rate was approximately 35%.

After mitigation:

Total current distortion rate is approximately 8%.

 

A N601治理前:a相基波电流含量170.93 A

A N601治理后:a相基波电流含量172.63 A

 

Before mitigation:

Phase A fundamental current content: 170.93A

Phase A 5th harmonic current content: 55.04A

Phase A 7th harmonic current content: 13.44A

Phase A 11th harmonic current content: 18.1A

 

 

After mitigation:

Phase A fundamental current content 172.63A

Phase A 5th harmonic current content 6.41A

Phase A 7th harmonic current content 2.25A

Phase A 11th harmonic current content 2.47A

 

 

Location:AN501

A N501治理前:三相电流波形有畸变

A N501治理后:三相电流波形趋于正弦波

Before mitigation:

The three-phase current waveforms were distorted.

After mitigation:

The three-phase current waveform tends to be sinusoidal.

 

A N501治理前:电流总畸变率42%左右

A N501治理后:电流总畸变率8%左右

Before mitigation:

Total current distortion rate was approximately 42%.

After mitigation:

Total current distortion rate is approximately 8%.

 

A N501治理前:b相基波电流含量90.52 A

A N501治理后:b相基波电流含量91.07 A

 

Before mitigation:

Phase B fundamental current content: 90.52A

Phase B 5th harmonic current content: 33.75A

Phase B 7th harmonic current content: 14.35A

Phase B 11th harmonic current content: 6.75A

 

 

After mitigation:

Phase B fundamental current content 91.07A

Phase B 5th harmonic current content 4.21A

Phase B 7th harmonic current content 1.95A

Phase B 11th harmonic current content 0.59A

 

 

Location:AC-CHP

Ac Chp治理前:电流波形有畸变

Ac Chp治理后:电流波形趋于正弦波

Before mitigation: 

The current waveform was distorted.

After mitigation: 

The current waveform tends to be sinusoidal.

 

Ac Chp治理前:电流总畸变率42%左右

Ac Chp治理后:电流总畸变率10%左右

Before mitigation:

Total current distortion rate was approximately 42%.

After mitigation:

Total current distortion rate is approximately 10%.

 

Ac Chp治理前:c相基波电流含量118.89 A

Ac Chp治理后:c相基波电流含量119.79 A

 

Before mitigation:

Phase C fundamental current: 118.89A

Phase C 5th harmonic current: 43.71A

Phase C 7th harmonic current: 18.36A

Phase C 11th harmonic current: 8.70A

 

 

After mitigation:

Phase C fundamental current: 119.79A

Phase C 5th harmonic current: 6.94A

Phase C 7th harmonic current: 3.18A

Phase C 11th harmonic current: 1.98A

 

 

Mitigation Result:The harmonics were effectively controlled, and communication between the HMI and PLC returned to normal.